OUTDOOR RF
Part Number: 60012
|
Max. DC operating voltage
|
Uc | 120 Vdc |
|
Frequency range
|
f | DC-3.5 GHz |
|
Insertion loss
|
< 0.2 dB |
|
|
Return loss
|
> 20 dB |
|
|
Impedance
|
50 ohms |
|
|
VSWR
|
<1.2:1 |
|
|
Max. load current @25°C
|
IL | 10 A |
|
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 20 kA |
|
Nominal discharge current
C2 Category
|
In | 5 kA |
|
Protection mode(s)
|
Common mode |
|
|
Protection level
@1kV/µs (C3)
|
Up | < 700 V |
|
Impulse current
2 x 10/350µs Test - D1 Category
|
Iimp | 1 kA |
|
Max Power
|
70 W |
|
|
Typical let through energy
(50 ohms) input 4kV 1.2/50μs - 2kA 8/20μs
|
320 µJ |
|
|
DC Pass
|
Yes |
|
|
Insulation resistance
|
IR | ≥10 GOhms |
|
RF SPD TYPE
|
UL497E LISTED |
|
|
VOLTS
|
(V) | 48 |
|
AC/DC/DC PV/RF
|
RF |
|
|
WIRES
|
1W+GROUND |
|
|
LINE CURRENT MAX
|
(A) | 10 |
|
AMBIENT MIN
|
(C) | -40 |
|
AMBIENT MAX
|
(C) | +85 |
|
IMAX
8/20µs
|
(kA) | 20 |
|
FREQUENCY RANGE
|
(GHz) | 0-4.0 |
|
INSERTION LOSS (@ FREQ)
|
(db) | <0.2 |
|
RETURN LOSS
|
(db) |
|
|
VSWR
|
<1.25:1 |
|
Technology
|
Gas discharge tube |
|
|
Connection to Network
|
Connector N Female/Female |
|
|
Mounting
|
Bulkhead or Bracket |
|
|
Operating temperature
|
Tu | -40/+85°C |
|
Protection rating
|
IP65 |
|
|
Outdoor application
|
Yes |
|
|
Failsafe mode
|
Short-circuit |
|
|
Contacts
|
Bronze/Surface Au-Ag |
|
|
Insulation material
|
PTFE |
|
|
TECHNOLOGY
|
GDT |
|
|
CONNECTION METHOD
|
SERIES CONNECTOR, BI-DIRECTIONAL |
|
|
MOUNTING
|
BULKHEAD, OPTIONAL BRACKET |
|
|
MATERIAL
|
Housing-Cu, Zn, Sn plated Brass |
|
|
NEMA RATING (IP RATING)
|
NEMA 6P (IP67) |
|
|
DIMENSIONS
|
See diagram |
|
|
WEIGHT
|
0.30 lbs |
|
Environmental standards
|
EU RoHS |
|
|
RohS compliance
|
Yes |
|
|
UL STANDARD
|
UL497E |
|
|
UL CATEGORY
|
QVLA |
|
|
UL FILE NUMBER
|
E349646 |
|
|
STANDARDS
|
NOM-003-SCFI-2014, NOM-001-SCFI-1993 |
|
Mounting
|
Bracket or Bulkhead through-hole |
|
|
Accessories
|
BK series mounting bracket |
Datasheet