- UL497E LISTED - Imax 20kA (10kA UL) - In 10kA (10kA UL) - Bi-directional - Replaceable Gas Tube
P8AX25-6G-T/MF
Part Number: 68304
- Gas Discharge Tube Technology, DC Pass
- Frequency Range 0-6.9GHz
- Imax 20kA, 10kA (UL), In 10kA
- IP67 Outdoor Rated
- N-Type Connector
- Bi-Directional
- Replaceable Gas Tube
Select another reference:
Frequency range | f | DC-7 GHz |
Insertion loss | 0.3 dB | |
Return loss | > 18 dB | |
Impedance | 50 ohms | |
VSWR | < 1.3:1 | |
Max. load current | IL | 10 A |
Max. discharge current | Imax | 20 kA |
Protection mode(s) | Common mode | |
Protection level | Up | < 2300 V |
Impulse current | Iimp | 1 kA |
Nominal discharge current | In | 5 kA |
Max Power | 240 W | |
DC Pass | ZERTZAERTZERTZER | True |
Insulation resistance | IR | ≥10 GOhms |
RF SPD TYPE | UL497E LISTED | |
VOLTS | (V) | 48 |
AC/DC/DC PV/RF | RF | |
WIRES | 1W+GROUND | |
LINE CURRENT MAX | (A) | 10 |
AMBIENT MIN | (C) | -40 |
AMBIENT MAX | (C) | +85 |
IN | (kA) | 10 |
IMAX | (kA) | 20 |
FREQUENCY RANGE | (GHz) | 0-6.9 |
INSERTION LOSS | (db) | <0.2 |
RETURN LOSS | (db) | >22 |
VSWR | <1.25:1 |
Technology | Gas discharge tube | |
Connection to Network | Connector TNC Male/Female | |
Mounting | Feedthrough | |
Housing material | Brass/Surface plating : Cu Zn Sn | |
Operating temperature | Tu | -40/+85°C |
Protection rating | IP66 | |
Outdoor application | Yes | |
Dimensions | See diagram | |
Contacts | Bronze/Surface Au-Ag | |
Insulation material | PTFE | |
TECHNOLOGY | GDT | |
CONNECTION METHOD | SERIES CONNECTOR, BI-DIRECTIONAL | |
MOUNTING | BULKHEAD, OPTIONAL BRACKET | |
MATERIAL | Cu, Zn, Sn plated Brass, PTFE | |
NEMA RATING (IP RATING) | NEMA 6P (IP67) | |
DIMENSIONS | See diagram (mm) | |
WEIGHT | 0.30 lbs |
Standards compliance | IEC 61643-21 / EN 61643-21 / UL497C / UL497E | |
RohS compliance | Yes | |
UL STANDARD | UL497E | |
UL CATEGORY | QVLA | |
UL FILE NUMBER | E349646 | |
STANDARDS | NOM-003-SCFI-2014, NOM-001-SCFI-1993 | |
ENVIRONMENTAL STANDARDS | ROHS |