UL TYPE 4CA - Imax 22kA - In 10kA

MLPC1-277L-V-Ex​
Part Number: 897017
MLPC1-277L-V-Ex​
Availability:
$155.00 (excl. tax)

Available within 3 weeks

  • UL121201 Hazardous Locations
  • UL1449 5th ed. Type 2 SPD
  • ANSI C136.2
  • 120 VAC to 277 VAC
  • Plate Mounting
  • Screw Terminal Connection
  • Series or Parallel Installation
  • Status indicator
  • Disconnection AC end of life
  • Total Surge Rating – Itotal: 20kA



POWER SPD TYPE
UL1449 TYPE 2 LISTED
VOLTS
(V) 277
AC/DC/DC PV/RF
AC
PHASE
(PH) 1
AMPS
(A) 5
AMBIENT MIN
(C) -40
AMBIENT MAX
(C) +85
MODES
L-L, L-G, L-N, N-G
VPR
(V) 1500/1500/1200
MCOV
(V) 385/385/255
IN
15 impulses 8/20µs
(kA) 5
SCCR
(kA) 18
IMAX
8/20µs
(kA) 10
TECHNOLOGY
MOV-GSG
NETWORK CONFIGURATION
2 pole, 2W+G, Single/Spilt Phase
CONNECTION METHOD
Screw Terminal (4-10AWG)
MOUNTING
FLANGE MOUNT
MATERIAL
Thermoplastic UL94-V0
NEMA RATING (IP RATING)
NEMA 2 (IP20)
FAIL-SAFE BEHAVIOR
Disconnection via fuse-link
REAL-TIME DIAGNOSTICS
LED Indicator
DIMENSIONS
See diagram
WEIGHT
0.30 lbs
Certification
UL 497B
UL STANDARD
UL1449 5th Edition & UL121201
UL CATEGORY
VZCA, VZCA7, VZCH, VZCH7
UL FILE NUMBER
E326289, E527348
UL121201 HAZARDOUS LOCATION
Class I, Division 2, Groups A, B, C & D: Operating Temp. T4A
STANDARDS
IEC 61643-11, NOM-003-SCFI-2014, NOM-001-SCFI-1993
ANSI/IEEE C62.41
Category C 20kV/10kA
ANSI/IEEE C136.2
Enhanced Category 10kV/5kA
ENVIRONMENTAL STANDARDS
ROHS