UL497B LISTED - Imax 20kA - In 5kA - Modular
Part Number: 6419041
DLAWS1-48D3
- Hybrid SAD-GDT Technology
- UL497B LISTED
- 20kA Imax (1x 8/20us)
- 5kA Imp (2x 10/350us)
- 5kA In (10x 8/20us)
- Modular with Visual Fault Indicator
- Spring & Screw Terminal versions
- Circuit disconnection with Module removal
- Common/Differential Mode Protection
|
Network
|
ISDN-T0, 48 V |
|
|
Nominal line voltage
|
Un | 48 V |
|
Max. DC operating voltage
|
Uc | 53 Vdc |
|
Max. frequency
|
f max. |
|
|
Insertion loss
|
< 1 dB |
|
|
Max. load current @25°C
|
IL | 300 mA |
|
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 20 kA |
|
Nominal discharge current
C2 Category
|
In | 5 kA |
|
Nominal Discharge Current, X-C (Line/Earth)
8/20µs Test x 10 - C2 Category
|
In L/PE | 5 kA |
|
Protection Level
C3 (10/1000μs), 300 applications@10 A, Y-Y (Line/Line)
|
Up | 70 V |
|
Protection Level
C3 (10/1000μs), 300 applications@10 A, Y-C (Line/Earth)
|
Up | 70 V |
|
Impulse current
D1 (10/350μs), 2 applications, X-C (Line/Earth)
|
Iimp | 5 kA |
|
Line resistance (± 10%)
|
4.7 Ohm |
|
Technology
|
GDT+Clamping diode+PTC (thermal resistor) + Resistor |
|
|
Connection to Network
|
By screw terminal: cross section 0.5-2.5mm² |
|
|
Format
|
Plug-in DIN box |
|
|
Mounting
|
Symmetrical rail 35 mm (EN 60715) |
|
|
Operating temperature
|
Tu | -40/+85°C |
|
Protection rating
|
IP20 |
|
|
Failsafe mode
|
Opening line - transmision cut-off - fault mode 2 |
|
|
NETWORK CONFIGURATION
|
1 pair |
|
|
MATERIAL
|
Thermoplastic UL94-V0 |
|
|
DIMENSIONS
|
See diagram |
|
|
SPARE PART
|
DLASM-48D3 |
|
Certification
|
UL Listed |
|
|
Environmental standards
|
EU RoHS |
|
|
UL STANDARD
|
UL497B |
|
|
UL CATEGORY
|
QVGQ |
|
|
UL FILE NUMBER
|
E184939 |
|
|
STANDARDS
|
IEC 61643-11, NOM-003-SCFI-2014, NOM-001-SCFI-1993 |
Datasheet