TRANSTECTOR 1101-626 I2R ICP 48VDC
Comparison CITEL DS230S-48DC
Surge Protective Device (SPD)

DS230S-48DC
CITEL DS230S-48DC
Surge Protector
1101-626 I2R ICP 48VDC
Surge Protector

Intended Application System

System Voltage48VDC
Number of Phases-
Conductors2 Wire + Ground
ConfigurationDC Power

PRODUCT COMPARISON TABLE

This page collects publicly available data from ul.com and assembles a side by side reference table for a convenient product cross reference.

Manufacturer Citel Logo TRANSTECTOR
UL File #E326289E220064
Model
DS230S-48DC


1101-626 I2R ICP 48VDC

Product Image DS230S-48DC

UL.com Ratings


UL CARD


UL CARD

UL APPROVALRecognized UL 1449 5th Ed.
UL 1449 4th Ed. Recognized Isolated Loop Circuit Protector
UL MARK UR logo png
SPD Type4CA
UL497B
Volt (V)48DC48DC
AC/DC
DC PV
DCDC
Phasen/an/a
Amps (A)n/an/a
Ambient Min (C)-40-40
Ambient Max (C)8580
Mode
MLV (Vpk)
DC+-DC-
DC+-G
DC--G
710
540
560
not tested per UL 1449
not tested UL 1449
not tested per UL 1449
MCOV
DC+-DC-
DC+-G
DC--G
65
65
65
not tested per UL 1449
not tested per UL 1449
not tested per UL 1449
In (kA)10-
SCCR (kA)n/a-

Additional
Data Sheet Ratings

Surge Current
Rating (kA)
30
2.5
Protection CircuitMOV
(Thermally Protected)
MOV
(Thermally Protected)
Leakage CurrentYesYes
TOV OptimizedNoNo
DiagnosticsIndicator &
Remote Contacts
Indicator
Environmental
Rating
IP20Manufacturer did not specify
# of Wires32
Modes of ProtectionCommon Mode
Differential Mode
Common Mode
Warranty10-years1-years
Notes
UL 1449 standard covers SPDs for power circuits not exceeding 1000 Vac and for PV applications up to 1500 Vdc.
UL 497B standard covers protectors for Data Communications and Fire-Alarm Circuits
.

Determining the acceptability of an SPD for your UL equipment

(for UL 508A Control Panels and All Other UL Listed Equipment)

The UL inspector will first consider the SPD type when determining it’s acceptability for a given application or piece of equipment. This will include UL 508A as well as all other UL Listed equipment. The first level compliance is based on the UL Approval (LISTED or RECOGNIZED) of the SPD or UL SPD Type and it’s Suitable Ratings. This means that it has to meet all safety, performance, environmental and electrical system ratings of the application. If any of these criteria are not fully met, it will require a Procedure Description, a File Update and/or Additional Testing. These actions will require additional costs that may be substantial. For this reason, it is in the interest of the specifier to use UL LISTED SPD’s to eliminate any uncertainty or to make sure the UL RECOGNIZED SPD is selected at the time of UL submittal of the equipment.

Approval Considerations Table based on UL SPD Type

UL
Mark
UL1449
SPD Type
Suitable
Ratings
Procedure
Described
File
Update or
Additional
Testing
Notes
1

2
YesNoNoThe only requirement is that the SPD must match electrical and environmental ratings of the UL 508A Control Panel.

A UL field inspection of the control panel with the SPD installed is required as a part of a standard follow-up service visit.
1CA

2CA

4CA

5
YesYesYesYes – All UL recognized SPD’s require a UL engineering evaluation of the SPD’s existing UL1449 E–file.

This will result, at a minimum, in a cost to update the UL file and may also require testing that would result in additional costs.
UL data is publicly available with a free account at UL.com. The data has been reviewed by our engineering department. From time to time, the applicants UL file (including CITEL's) may become changed or updated at UL.com due to new testing or corrections to a report. At the time of this comparison you will find this information to be accurate to the UL web site. If you find any information requires an update, please bring to our attention and it will be updated immediately.

Citel Logo
10108 USA Today Way
Miramar, FL 33025 USA
Contact us to develop a surge mitigation solution for your application

www.citel.us

Where to purchase Citel SPD's