UL497B LISTED - Imax 20kA - In 5kA - Modular

DLC-06D3
Part Number: 641101
DLC-06D3
Availability:
$75.00 (excl. tax)

Call for leadtime/delivery

  • Hybrid Technology
  • Compact 6mm module
  • UL497B LISTED
  • 10kA Imax (1x 8/20us)
  • 2.5kA Imp (2x 10/350us)
  • 5kA In (10x 8/20us)
  • 2W+SHIELD+G
  • Common/Differential mode protection



Network

RS422, RS485

Nominal line voltage
Un

6 V

Max. DC operating voltage
Uc

8 Vdc

Cut-off frequency
-3dB, 100 ohm system
f max.

> 100 MHz

Cut-off frequency
-1dB, 100 ohm system
f max.

> 45 MHz

Insertion loss

< 1 dB

Max. load current @25°C
IL

300 mA

Max. discharge current
max. withstand @ 8/20 µs by pole
Imax

10 kA

Nominal Discharge Current, X-C (Line/Earth)
8/20µs Test x 10 - C2 Category
In L/PE

5 kA

Protection Level
C3 (10/1000μs), 300 applications@10 A, Y-Y (Line/Line)
Up

25 V

Protection Level
C3 (10/1000μs), 300 applications@10 A, Y-C (Line/Earth)
Up

25 V

Impulse current
2 x 10/350µs Test - D1 Category
Iimp

2.5 kA

Line resistance (± 10%)

4.7 Ohm

Technology

GDT+TVS diode

Connection to Network

By spring terminal - max. cross section 2.5mm² / AWG 13 (solid or stranded)

Format

DIN box

Mounting

Symmetrical rail 35 mm (EN 60715)

Operating temperature
Tu

-40/+85°C

Ingress Protection rating

IP20 (NEMA 2)

Failsafe mode

Short-circuit

NETWORK CONFIGURATION

1 pair

MATERIAL

Thermoplastic UL94-V0

DIMENSIONS

See diagram

Certification

UL Listed

Environmental standards

EU RoHS

UL STANDARD

UL497B

UL CATEGORY

QVGQ

UL FILE NUMBER

E184939

STANDARDS

IEC 61643-11, NOM-003-SCFI-2014, NOM-001-SCFI-1993