- UL497B LISTED - Imax 20kA - In 5kA - Modular - Data Speed 10/100/1000
Part Number: 640331
DLA2-24DBC
- Hybrid SAD-GDT Technology
- UL497B LISTED
- 20kA Imax
- 5kA Imp
- 5kA In
- Modular
- 4W+SHIELD+G
|
Network
|
Fipway, WorldFIP, FieldBus-h2 |
|
|
Nominal line voltage
|
Un | 24 V |
|
Max. DC operating voltage
|
Uc | 28 Vdc |
|
Max. frequency
|
f max. |
|
|
Insertion loss
|
< 1 dB |
|
|
Max. load current @25°C
|
IL | 300 mA |
|
Max. discharge current
max. withstand @ 8/20 µs by pole
|
Imax | 20 kA |
|
Nominal discharge current
C2 Category
|
In | 5 kA |
|
Protection Level
C3 (10/1000μs), 300 applications@10 A, Y-Y (Line/Line)
|
Up | 75 V |
|
Protection Level
C3 (10/1000μs), 300 applications@10 A, Y-C (Line/Earth)
|
Up | 650 V |
|
Max. capacitance
|
C | < 50 pF |
|
Impulse current
2 x 10/350µs Test - D1 Category
|
Iimp | 5 kA |
|
Impulse current
D1 (10/350μs), 2 applications, X-C (Line/Earth)
|
Iimp | 5 kA |
|
Line resistance (± 10%)
|
4.7 Ohm |
|
|
WIRES
|
4W+SHIELD+GROUND |
|
|
FREQUENCY
|
(MHz) |
|
|
Network type
|
Data Communication |
|
|
Technology
|
GDT+TVS diode |
|
|
Connection to Network
|
By screw terminal: cross section 0.5-2.5mm² |
|
|
Format
|
Plug-in DIN box |
|
|
Mounting
|
Symmetrical rail 35 mm (EN 60715) |
|
|
Operating and storage temperature
|
-40/+85°C |
|
|
Protection rating
|
IP20 |
|
|
Failsafe mode
|
Short-circuit |
|
|
NETWORK CONFIGURATION
|
2 Channels (4W+G) |
|
|
CONNECTION METHOD
|
Screw Terminal |
|
|
MOUNTING
|
Din Rail |
Datasheet