Citel Logo

Comparison ABB OVR PV T2 40-1500 P Alternate CITEL DS50PVS-1500/51

${ITEM_LINK#2179040}<-No Item, #2179040 DS50PVS150051 ABB_OVR-PV-T2-40-1500P
CITEL DS50PVS-1500/51
DC PV Surge Protector
ABB OVR PV T2 40-1500 P
DC PV Surge Protector

Intended Application System

System Voltage1500Vdc PV
Number of PhasesDC+. DC-, G
Conductors2 Wire + Ground
ConfigurationDC PV

PRODUCT COMPARISON

This page collects publicly available data from ul.com and manufacturers’ web sites then assembles a side by side reference table for convenient product comparisons.
Brand Citel Logo abb
ManufacturerCITEL AMERICA INCABB STOTZ-KONTAKT GmbH
Location10108 USA Today Way
Miramar FL 33025
USA
ABB, Eppelheimer Str. 82,
Heidelberg 69123
DE
UL File #E326289E316468
ModelDS50PVS-1500/51
OVR PV
T2 40-1500 P

Product Image${ITEM_LINK#1651181${IMG#2582067,STYLE:'width:95px;height:110px'}<-Unexpected symbol found!, ERROR: '${IMG#2582067,STYLE:'width:95px;height:110px'' ABB_OVR-PV-T2-40-1500P

UL.com Ratings

UL CARDUL CARD
SPD Type1CA1CA
UL Mark cURus cURus
Volt (V)15001500
AC/DC
DC PV
DC
DC PVDC PV
Phase--
Amps (A)n/an/a
Ambient Min (C)-40-40
Ambient Max (C)8585
Mode
DC+-DC-
DC+-G
DC--G
DC+-DC-
DC+-G
DC--G
DC+-DC-
DC+-G
DC--G
VPR (Vpk)
DC+-DC-
DC+-G
DC--G
4000
4000
4000
4000
4000
4000
MCOV
DC+-DC-
DC+-G
DC--G
1500
1500
1500
1500
1500
1500
In (kA)1010
SCCR (kA)100
10

Additional
Data Sheet Ratings

Surge Current
Rating (kA)
4040
Protection CircuitTMOVTMOV
Circuit Diagram DS50PVS-1500-51_elec ABB_OVR-PV-T2-40-1500P_CIRCUIT-DIAGRAM
Leakage CurrentYesYes
TOV OptimizedNoNo
DiagnosticsVisual Indicator
Remote Alarm
Visual Indicator
Environmental
Rating
IP20IP20
Warranty10-years
12 months
after installation
18 months
after shipment
"UL.com Ratings" data is publicly available with a free account at UL.com. The "Additional Data Sheet Ratings" are available for free on the manufacturers web site or by submitting a request directly. All the data has been reviewed by our engineering department. From time to time, the applicants UL file (including CITEL's) may become changed or updated at UL.com due to new testing or corrections to a report. In addition, manufacturers may change the data on their web sites. At the time of this comparison you will find this information to be accurate to the UL web site as well as the manufacturers publicly available data. If you find any information requires an update, please bring to our attention and it will be updated immediately.

Determining the acceptability of an SPD
for UL 1449 Surge Protective Devices and All Other UL Listed Equipment

The UL inspector will first consider the SPD type when determining it’s acceptability for a given application or piece of equipment. This will include UL1449 as well as all other UL Listed equipment. The first level compliance is based on the UL Approval (LISTED or RECOGNIZED) of the SPD or UL SPD Type and it’s Suitable Ratings. This means that it has to meet all safety, performance, environmental and electrical system ratings of the application. If any of these criteria are not fully met, it will require a Procedure Description, a File Update and/or Additional Testing. These actions will require additional costs that may be substantial. For this reason, it is in the interest of the specifier to use UL LISTED SPD’s to eliminate any uncertainty or to make sure the UL RECOGNIZED SPD is selected at the time of UL submittal of the equipment.

Approval Considerations Table based on UL SPD Type

UL
Mark
UL1449
SPD Type
Suitable
Ratings
Procedure
Described
File
Update or
Additional
Testing
Notes
1

2
YesNoNoThe only requirement is that the SPD must match electrical and environmental ratings.

A UL field inspection of the equipment with the SPD installed is required as a part of a standard follow-up service visit.
1CA
2CA
4
5
Yes
Yes
Yes
Yes – All UL recognized SPD’s require a UL engineering evaluation of the SPD’s existing UL1449 E–file.

This will result, at a minimum, in a cost to update the UL file and may also require testing that would result in additional costs.


Citel Logo
10108 USA Today Way
Miramar, FL 33025 USA
Contact us to develop a surge mitigation solution for your application

www.citel.us

Where to purchase Citel SPD's