UL TYPE 2 LISTED SPD - Imax 105kA per phase - In 20kA - NEMA 3R/4/12
Part Number: 890188
MS80F-120Y
- Multi-TMOV Technology
- UL1449 Type 2 LISTED
- UL1283 LISTED EMI/RFI Filter
- BABA-Build America-Buy America compliant
- 105kA Surge Current Rating
- Connection Type-Parallel
- Operating Freqency-47Hz-63Hz
- Response time- <50 ns
- Visual fault indicator
- 10-Year warranty
|
POWER SPD TYPE
|
UL1449 TYPE 2 LISTED |
|
|
VOLTS
|
(V) | 120/208 |
|
AC/DC/DC PV/RF
|
AC |
|
|
PHASE
|
(PH) | 3Y |
|
AMPS
|
(A) | N/A |
|
AMBIENT MIN
|
(C) | -40 |
|
AMBIENT MAX
|
(C) | +85 |
|
MODES
|
L-L, L-N, L-G, N-G |
|
|
VPR
|
(V) | 1000/700/700/700 |
|
MCOV
|
(V) | 300/150/150/150 |
|
IN
15 impulses 8/20µs
|
(kA) | 20 |
|
IMAX
8/20µs
|
(kA) | 105 |
|
Iimp
10/350µs
|
(kA) | 4 |
|
TECHNOLOGY
|
Multi-TMOV |
|
|
NETWORK CONFIGURATION
|
3PH, 4W+G, Wye |
|
|
CONNECTION METHOD
|
36" #10 AWG LEADS |
|
|
MOUNTING
|
FLANGE MOUNT |
|
|
MATERIAL
|
Steel |
|
|
NEMA RATING (IP RATING)
|
IP65 |
|
|
FAIL-SAFE BEHAVIOR
|
Yes, no upstream over current protection required |
|
|
REAL-TIME DIAGNOSTICS
|
% of protection present LED, audible alarm and remote contacts. Optional surge counter. |
|
|
DIMENSIONS
|
See diagram |
|
|
WEIGHT
|
6 lbs |
|
Certification
|
UL Listed |
|
|
Environmental standards
|
EU RoHS |
|
|
UL STANDARD
|
UL1449 5th Edition, UL1283 |
|
|
UL CATEGORY
|
VZCA, VZCA7, FOKY, FOKY7 |
|
|
UL FILE NUMBER
|
E326289 |
|
|
STANDARDS
|
UL96A, ANSI C62.41/45, NOM-003-SCFI-2014, NOM-001-SCFI-1993 |
Datasheet