UL121201 Hazardous Locations- Imax 40kA - In 20kA - Modular

DS240S-120-Ex
Part Number 897006
DS240S-120-Ex
Availability:
$331.70 (excl. tax)

Available within 3 weeks

  • UL121201 Hazardous Locations
  • MOV Technology
  • UL1449 Type 4CA
  • 40kA Surge Current Rating
  • Visual fault indicator and remote contacts
  • 10-Year warranty



Network

120 V single-phase

Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total

80 kA

Protection mode(s)

Common mode

Residual voltage at 5 kA
@ 5 kA (8/20µs)
Up-5kA

0.6 kV

POWER SPD TYPE

UL1449 5th Ed. TYPE 4CA

VOLTS
(V)

240/120

AC/DC/DC PV/RF

AC

PHASE
(PH)

1S

AMPS
(A)

N/A

AMBIENT MIN
(C)

-35

AMBIENT MAX
(C)

+60

MODES

L-L, L-N, L-G, N-G

MLV
(V)

2010/1580/2010/1580

MCOV
(V)

300/150/300/150

IN
15 impulses 8/20µs
(kA)

20

SCCR
(kA)

n/a

IMAX
8/20µs
(kA)

40

Technology

MOV

Connection to Network

By screw terminals: 1.5-10mm² (L/N) or 2.5-25mm² (PE)

Format

Plug-in modular box

Failsafe mode

Disconnection from AC network

Weight

0.118 kg

TECHNOLOGY

MOV

NETWORK CONFIGURATION

1PH, 2W+G, Single Phase (or 2PH, 2W+G, Two Phase)

CONNECTION METHOD

Screw Terminal, 15-5AWG Solid Wire, 15-7AWG Stranded Wire

MOUNTING

Din Rail

MATERIAL

Thermoplastic UL94-V0

NEMA RATING (IP RATING)

NEMA 2 (IP20)

FAIL-SAFE BEHAVIOR

Disconnection via fuse-link

REAL-TIME DIAGNOSTICS

Visual indicator and remote contacts

DIMENSIONS

See diagram

WEIGHT

0.30 lbs

SPARE PART

DSM240-120

Certification

UL Recognized

UL STANDARD

UL1449 5th Edition & UL121201

UL CATEGORY

VZCA2, VZCA8, VZCH, VZCH7

UL FILE NUMBER

E326289, E527348

UL121201 HAZARDOUS LOCATION

Class I, Division 2, Groups A, B, C & D: Operating. Temp. T5

STANDARDS

NOM-003-SCFI-2014, NOM-001-SCFI-1993

ENVIRONMENTAL STANDARDS

ROHS