3 ELECTRODE GDT

BM CMS(T&R) 420/20
Part Number: 929711801
BM CMS(T&R) 420/20



DC sparkover voltage (100V/s)
336-504 V
DC spark voltage tolerance
+/- 20%
Maximum impulse sparkover voltage (1kV/µs)
<1000 V
Nominal discharge current
10 x 8/20µs impulses
In 10 kA
Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total 25 kA
Impulse discharge current
10/350µs - 1 time
2 kA
Max. capacitance
C <0.5 pF
Insulation resistance
IR ≥10 GOhms
Arc Voltage
≤ 25 V
Glow-to-arc transition current
0.5 A
Glow voltage
≤ 100 V
AC discharge current (50Hz)
10 A
DC Holdover voltage
R = 300 ohms in serie R = 150 ohms; 100nF en parrallel
>80 V
Impulse life
300 times, interval 2 min
50 A
Operating and storage temperature
-40°C / +90°C
RohS compliance
Yes