2 ELECTRODE GDT




DC sparkover voltage (100V/s)
376-564 V
DC spark voltage tolerance
+/- 20%
Maximum impulse sparkover voltage (1kV/µs)
<1000 V
Nominal discharge current
10 x 8/20µs impulses
In 20 kA
Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total 40 kA
Max. capacitance
C <0.8 pF
Insulation resistance
IR ≥10 GOhms
Arc Voltage
≤ 25 V
Glow voltage
≤ 120 V
AC discharge current (50Hz)
20 A
DC Holdover voltage
R = 300 ohms in serie R = 150 ohms; 100nF en parrallel
>80 V
Operating and storage temperature
-40°C / +90°C
Weight
1.25 g
Certification
UL Recognized / ROHS
RohS compliance
Yes