PANELMOUNT AC
Select another reference:
POWER SPD TYPE | UL1449 TYPE 2 LISTED | |
VOLTS | (V) | 120/208 |
AC/DC/DC PV/RF | AC | |
PHASE | (PH) | 3Y |
AMPS | (A) | n/a |
AMBIENT MIN | (C) | - |
AMBIENT MAX | (C) | - |
MODES | L-L, L-N, L-G, N-G | |
VPR | (V) | 1800/800/900/800 |
MCOV | (V) | 300/150/150/150 |
IN | (kA) | 5 |
IMAX | (kA) | 200 |
TECHNOLOGY | MOV | |
NETWORK CONFIGURATION | 3PH, 4W+G, Wye | |
CONNECTION METHOD | 36" #10 AWG LEADS | |
MOUNTING | FLANGE MOUNT | |
MATERIAL | Carbon steel | |
NEMA RATING (IP RATING) | 1/12 | |
FAIL-SAFE BEHAVIOR | 30A upstream overcurrent device | |
REAL-TIME DIAGNOSTICS | LED, audible alarm and remote contacts. | |
DIMENSIONS | See diagram (mm) | |
WEIGHT | 8 lbs |
UL STANDARD | UL1449 4th Edition | |
UL CATEGORY | VZCA, VZCA7 | |
UL FILE NUMBER | E326289 | |
STANDARDS | NOM-003-SCFI-2014, NOM-001-SCFI-1993 | |
ENVIRONMENTAL STANDARDS | ROHS |