DEHN 952 565 Alternate CITEL DS50PVS-1500/51

Citel Logo

DEHN 952 565 Comparison CITEL DS50PVS-1500/51
Surge Protectors for EV Charging Station (DC Power)

DS50PVS150051 Dehn_952567_DG-M-YPV-1500-FM
CITEL DS50PVS-1500/51
Surge Protector
DEHN 952 565
Surge Protector

Intended Application System

System Voltage1000Vdc
Number of PhasesDC+, DC-, G
Conductors2 Wires + Ground
ConfigurationDC PV

PRODUCT COMPARISON TABLE

This page collects publicly available data from ul.com and assembles a side by side reference table for a convenient product cross reference.

Brand Citel Logo Dehn
ManufacturerCITEL AMERICA INCDEHN SE
Location10108 USA Today Way
Miramar FL 33025
USA
Hans-Dehn-Strasse 1,
Neumarkt Bayern 92318
DE
UL File #E326289E319777
Model DS50PVS-1500/51DEHN 952 565
Product Image DS50PVS150051 Dehn_952567_DG-M-YPV-1500-FM

UL.com Ratings


UL CARD


UL CARD

UL APPROVALLISTEDRECOGNIZED
UL MARK cULus cURus
SPD Type11CA
Volt (V)15001170
AC/DCDC
-
DC PVDC PVDC PV
Phase--
Amps (A)n/an/a
Ambient Min (C)-40-40
Ambient Max (C)7585
Mode
DC+-DC-
DC+-G
DC--G
DC+-DC-
DC+-G
DC--G
VPR (Vpk)
DC+-DC-
DC+-G
DC--G
4000
4000
4000
3000
3000
3000
MCOV
DC+-DC-
DC+-G
DC--G
1500
1500
1500
1170
1170
1170
In (kA)1010
SCCR (kA)n/an/a

Additional
Data Sheet Ratings

Surge Current
Rating (kA)
4040
Protection CircuitTMOVTMOV
Leakage CurrentYesYes
TOV OptimizedNoNo
DiagnosticsIndicator
Remote Contacts
Indicator
Remote Contacts
Environmental
Rating
IP20IP20
# of Wires33
Modes of ProtectionCommon Mode
Differential Mode
Common Mode
Differential Mode
Warranty10-years5-years
Notes
DC Rating : Direct current
DC PV ratings : Direct current for use in photovoltaic applications only

Determining the acceptability of an SPD for your UL equipment for UL 508A Control Panels and All Other UL Listed Equipment

The UL inspector will first consider the SPD type when determining it’s acceptability for a given application or piece of equipment. This will include UL 508A as well as all other UL Listed equipment. The first level compliance is based on the UL Approval (LISTED or RECOGNIZED) of the SPD or UL SPD Type and it’s Suitable Ratings. This means that it has to meet all safety, performance, environmental and electrical system ratings of the application. If any of these criteria are not fully met, it will require a Procedure Description, a File Update and/or Additional Testing. These actions will require additional costs that may be substantial. For this reason, it is in the interest of the specifier to use UL LISTED SPD’s to eliminate any uncertainty or to make sure the UL RECOGNIZED SPD is selected at the time of UL submittal of the equipment.

Approval Considerations Table based on UL SPD Type

UL
Mark
UL1449
SPD Type
Suitable
Ratings
Procedure
Described
File
Update or
Additional
Testing
Notes
1

2
YesNoNoThe only requirement is that the SPD must match electrical and environmental ratings of the UL 508A Control Panel.

A UL field inspection of the control panel with the SPD installed is required as a part of a standard follow-up service visit.
1CA

2CA

4CA

5
YesYesYesYes – All UL recognized SPD’s require a UL engineering evaluation of the SPD’s existing UL1449 E–file.

This will result, at a minimum, in a cost to update the UL file and may also require testing that would result in additional costs.
UL data is publicly available with a free account at UL.com. The data has been reviewed by our engineering department. From time to time, the applicants UL file (including CITEL's) may become changed or updated at UL.com due to new testing or corrections to a report. At the time of this comparison you will find this information to be accurate to the UL web site. If you find any information requires an update, please bring to our attention and it will be updated immediately.

Citel Logo
10108 USA Today Way
Miramar, FL 33025 USA
Contact us to develop a surge mitigation solution for your application

www.citel.us

Where to purchase Citel SPD's