2 ELECTRODE GDT

BHSQ CMS (T&R) 600/20
Part Number: 929987701
BHSQ CMS (T&R) 600/20



DC sparkover voltage (100V/s)
480-720 V
DC spark voltage tolerance
+/- 15%
Maximum impulse sparkover voltage (1kV/µs)
<1200 V
Nominal discharge current
10 x 8/20µs impulses
In 20 kA
Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total 25 kA
Max. capacitance
C <0.8 pF
Insulation resistance
IR ≥10 GOhms
Arc Voltage
≤ 25 V
Glow voltage
≤ 120 V
AC discharge current (50Hz)
20 A
DC Holdover voltage
R = 300 ohms in serie R = 150 ohms; 100nF en parrallel
>80 V
Operating and storage temperature
-40°C / +90°C
Certification
UL1283
RohS compliance
Yes