2 ELECTRODE GDT

BH 2500/20
Part Number: 9285538
BH 2500/20



DC sparkover voltage (100V/s)
2000-3000 V
DC spark voltage tolerance
+/- 20%
Maximum impulse sparkover voltage (1kV/µs)
<3800 V
Nominal discharge current
10 x 8/20µs impulses
In 10 kA
Total Maximum discharge current
max. total withstand @ 8/20 µs
Imax Total 25 kA
Max. capacitance
C <0.8 pF
Insulation resistance
IR ≥10 GOhms
Arc Voltage
≤ 50 V
Glow voltage
≤ 250 V
AC discharge current (50Hz)
10 A
DC Holdover voltage
R = 300 ohms in serie R = 150 ohms; 100nF en parrallel
>120 V
Operating and storage temperature
-40°C / +90°C
Weight
1.54 g
RohS compliance
Yes